 HVA 60 - High Voltage VLF and DC Hipot Test Instrument

The HVA60 is not only the most advanced HV test system available, it is also the lightest, most compact instrument of its type on the market. The HVA60 has the highest power to weight ratio of any comparable unit available.

Apart from the variable frequency VLF output, the operator can also select dual polarity DC and cable jacket or sheath testing outputs modes.

The applied test voltage, current, capacitance, resistance and time are displayed and recorded.The instrument is easily programmable allowing the operator to setup or select test sequences in either automatic or manual mode.

The HVA60 is capable of testing 1µF (Approx. 10,000 ft/ 3000m of cable) at 0.1Hz and 60kV peak. The frequency of the output can also be reduced allowing even larger capacitance loads to be tested. At 0.02Hz, approx. 50,000 ft/15,000m of cable can be tested.

Should a breakdown occur during testing, the actual voltage at which it occurred is displayed and recorded. If cable burning (fault conditioning) mode is activated, the fault resistance can be conditioned to allow easier and less stressful fault location techniques to be applied.

Test results are stored in the instrument’s onboard memory allowing easy retrieval and download to a PC/Laptop for review and analysis.

FEATURES:

The smallest, lightest, most advanced universal high voltage test i

nstrument available, ideally suited for a variety of applications.

VLF (0.1Hz), DC (±), Cable Fault Conditioning (Burning), and

Sheath/Jacket Testing modes all included.

VLF: the proven and accepted replacement for the traditional 
DC Hipot or “proof” test for solid dielectric cables such as XLPE
and EPR.

Fully Automatic or manual cable test sequences complying with

International Standards/Guides such as IEEE 400.2, VDE 0296, 
CENELEC, etc.

Meets all your cable testing requirements.

True Symmetrical Sinusoidal, load independent, output waveform 
across the full load range.

Real-time Display of actual output waveform.

Easy to use, ergonomic, menu guided, large backlit user interface

© Cable Diagnostics. All Rights Reserved. Designed by Glenn Goodwin Web Solutions

Tan Delta Bridge, Measurement Systems, VLF Hipot, smallest and lightest portable cable test, diagnostic solution, high voltage test sets, hipots, insulation testers, megohmmeters, vlf test equipment, very low frequency test systems, dc hipotential test equipment, ac/dc test sets, capacitor discharge system, maintenance tests, loss angle, dissipation factor in power cables, deterioration of aged cables, new cable installations, degradation of the insulation, why choose vlf or tan delta